Firetox Flame Retardant Cables 


Firetox Flame Retardant Cables

LSZH Flame Retardant CAT5E CWB/SWB/SWA Armoured Data Cables

FTX-CAT5EU/UTP4P24LH CWB/SWB/SWA

FTX-CAT5EF/UTP4P24LH CWB/SWB/SWA

FTX-CAT5ESF/UTP4P24LH CWB/SWB/SWA

APPLICATION

Cat5E is a cable standard for Gigabit Ethernet and other network protocol, suitable for basic voice and data

installations up to 100 MHz. In addition, these cables can be offered with copper wire braid armoured & flame

retardant outer sheath, providing additional mechanically protection still maintaining the flexibility of the cable.

STANDARDS

ISO/IEC 11801 EN 50173 ANSI/TIA/EIA 568

FTX-CAT5EU/UTP4P24LH CWB/SWB/SWA

FTX-CAT5EF/UTP4P24LH CWB/SWB/SWA

FTX-CAT5ESF/UTP4P24LH CWB/SWB/SWA

FIRE PERFORMANCE


Flame Retardance (Single vertical wire or cable test)

IEC 60332-1-2; EN 60332-1-2

Reduced Fire Propagation (Vertically-mounted bundled wires & cables test)

IEC 60332-3-24; EN 60332-3-24

Halogen Free

IEC 60754-1; EN 50267-2-1

No Corrosive Gas Emission

IEC 60754-2; EN 50267-2-2

Minimum Smoke Emission

IEC 61034-2; EN 61034-2

CABLE CONSTRUCTION

FTX-CAT5EU/UTP4P24LH CWB/SWB/SWA

FTX-CAT5EF/UTP4P24LH CWB/SWB/SWA

FTX-CAT5ESF/UTP4P24LH CWB/SWB/SWA

Conductors : 24AWG solid bare copper.

Insulation : PE.

Twinning : Two coloured insulated conductors twisted together to form a pair.

Inner Sheath : Thermoplastic LSZH compound.

Armouring :

CWB : Copper Wire Braid

SWB : Steel Wire Braid

SWA : Steel Wire Armour

Outer Sheath : Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound

type SW2-SW4 as per BS 7655-2.6 can be offered).

Outer Sheath Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite

properties can be offered as option.

Cat5EF/UTP : These cables have collective shielding of Aluminium/polyester tape with drain wire.

Cat5ESF/UTP : These cables have double collective shielding of Aluminium/polyester tape & copper wire braid.

PHYSICAL AND THERMAL PROPERTIES

Temperature range : -30°C - +75°C

Minimum bending radius during installation (mobile state) : 8 x Overall Diameter

Minimum bending radius during operation (fixed state) : 4 x Overall Diameter

ELECTRICAL PROPERTIES

AWG

 

24

Nominal Conductor Diameter

mm

0.50/0.51/0.53

Maximum DC Resistance@20°C

Ω/100m

9.38

Maximum DCR Unbalance

%

5

Maximum Mutual Capacitance

pF/m

55.8

Maximum Capacitance Unbalance

pF/100m

330

Characteristic Impedance@1-100MHz

Ω

100±15

Maximum Propagation Delay Skew

ns/100m

45

TRANSMISSION PROPERTIES

FREQ

Attenuation

NEXT

PSNEXT

ELFEXT

PSELFEXT

RL

MHz

dB/100m

dB

dB

dB/100m

dB/100m

dB

0.772

1.8

67.0

64.0

66.0

63.0

1

2.0

65.3

62.3

63.8

60.8

20.0

4

4.1

56.3

53.3

51.7

48.7

23.0

8

5.8

51.8

48.8

45.7

42.7

24.5

10

6.5

50.3

47.3

43.8

40.8

25.0

16

8.2

47.3

44.3

39.7

36.7

25.0

20

9.3

45.8

42.8

37.7

34.7

25.0

25

10.4

44.3

41.3

35.8

32.8

24.3

31.25

11.7

42.9

39.9

33.9

30.9

23.6

62.5

17.0

38.4

35.4

27.8

24.8

21.5

100

22.0

35.3

32.3

23.8

20.8

20.1

CONSTRUCTION PARAMETERS

Cable Code

Construction No. of Elements×No. of Cores in Element×Conductor Diameter

Nominal Insulation Thickness

Nominal Inner Sheath Thickness

Nominal Outer Sheath Thickness

Aprrox. Overall Diameter

Nominal Weight

mm

mm

mm

mm

mm

kg/km

FTX-CAT5EU/UTP4P24LH CWB

4×2×0.5

0.2

0.6

1.0

7.68

102

FTX-CAT5EU/UTP4P24LH SWB

4×2×0.5

0.2

0.6

1.0

7.68

98

FTX-CAT5EU/UTP4P24LH SWA

4×2×0.5

0.2

0.6

1.0

8.68

170

FTX-CAT5EF/UTP4P24LH CWB

4×2×0.53

0.2

0.6

1.0

8.28

121

FTX-CAT5EF/UTP4P24LH SWB

4×2×0.53

0.2

0.6

1.0

8.28

117

FTX-CAT5EF/UTP4P24LH SWA

4×2×0.53

0.2

0.6

1.0

9.28

197

FTX-CAT5ESF/UTP4P24LH CWB

4×2×0.53

0.2

0.6

1.0

8.76

128

FTX-CAT5ESF/UTP4P24LH SWB

4×2×0.53

0.2

0.6

1.0

8.76

124

FTX-CAT5ESF/UTP4P24LH SWA

4×2×0.53

0.2

0.6

1.0

9.76

221